Ventilation concepts for ventilation planning

The developments in recent years have led to an increasingly airtight building envelope (facade, windows, roof) in new buildings and after modernization. The clear goal is to keep heat losses as low as possible. At the same time, however, a change of air is absolutely necessary in order to avoid excessive humidity inside and the associated risk of mold formation. For this reason, the Energy Saving Ordinance (EnEV) regulates that “a minimum air exchange required for health and heating purposes is ensured” (EnEV 2014, Section 6, Paragraph 2). In order to determine this, a so-called ventilation concept must be created. The concept is required for all new buildings as well as for the renovation of single and multi-family houses, when more than a third of the windows are replaced or there is a major roof renovation with more than a third of the roof area. A simple reference to regular window ventilation by the user is not permitted according to the EnEV.

Specifically, the ventilation concept assesses whether the airflow rate resulting from air leakage in the building envelope (infiltration) exceeds the air exchange rate required for moisture protection. If this is not the case, the implementation of ventilation measures becomes mandatory. These measures encompass technical solutions for natural or fan-assisted ventilation designed to ensure air exchange that is independent of user behavior.

Produktion eines Keramikwärmespeichers von inVENTer

Calculation of the air exchange requirement

As a rule of thumb, an air exchange rate of 30 cubic meters per person per hour is required. The standard method for calculating the necessary outdoor air flow rate is the so-called Pettenkofer method. This method specifically takes into account the amount of carbon dioxide (CO2) exhaled by humans, which averages 20 liters of CO2 per hour (VCO2 = 0.02 m³/h).

The following formula is used:

Lüftungsplanung - Berechnung des Luftaustauschbedarfs

Meaning:

VCO2 02 quantity
VAU Required outside air volume flow
k CO2 permissible CO2 concentration in the room
k CO2 AU Concentration of CO2 in the outside air

The value for the permissible CO2 concentration in the room is:

kCO2 perm = 1000 cm3 CO2 / m3 air

The outside air usually contains a concentration of 300 to 400 cubic centimeters of CO2 per cubic meter of air. A concentration of is usually used for the calculation.

kCO2 AU = 0.00035 cm3 CO2 / m3 air

According to these specifications, a required outside air volume flow of around 123 cubic meters per hour results for a 4-person household:

Outdoor air typically contains a concentration of 300 to 400 cubic centimeters of CO₂ per cubic meter of air. A concentration of the following value is usually assumed for the calculation:

  • kCO2 AU = 0.00035 cm3 CO2 / m3 air

Based on these specifications, the required outdoor air volume flow for a 4-person household amounts to a total of approximately 123 cubic meters per hour:

Lüftungsplanung - Beispielberechnung für einen Luftaustausch

Moisture protection through air change based on an example

A family of four generates between 6,000 and 12,000 grams of water daily—that is, up to 12 liters. This is equivalent to a well-filled bucket of water. In homes sealed to meet energy-efficiency standards, simply opening windows regularly is no longer sufficient to adequately regulate humidity; otherwise, ventilation would be required every two hours—including at night, while at work, or during vacations. In such cases, an automatic ventilation system is essential.

Wasserdampfmenge im einer Familie

Data acquisitionto create a ventilation concept

Lüftungsplanung und Lüftungskonzept von inVENTer

The first step in gathering data on the building for the purpose of creating a ventilation concept involves considering geographical conditions. By cross-referencing the building’s postcode with a wind map—using data from the German Weather Service (DWD)—it is determined whether the building is located in a region with high or low wind exposure. Another factor is the orientation of the façade and its windows, which is assessed to ensure that natural ventilation is feasible. This type of ventilation is only possible if a residential or functional unit has windows on at least two sides of the façade, allowing air to flow from one side to the other driven by natural forces such as wind and temperature differences (cross-ventilation). Finally, details regarding thermal insulation and the number of floors within the residential or functional unit are recorded, distinguishing between single-story units and multi-story units.

With the final information on living space, the number of rooms and their allocation to the three usage categories wet room (kitchen or bathroom), living room (living room, bedroom or children’s room) and ancillary room, the data acquisition is complete.

Key data of ventilation planning

The planning proposals for optimal ventilation are based on generally applicable standards. These include the standards DIN 4701-10 for the energetic assessment of the building, DIN 18017-3 for indoor bathrooms and DIN 1946-6 for the free and fan-assisted ventilation of apartments. In addition, there are the requirements of the EnEV and requirements for subsidies, for example the Reconstruction Loan Corporation (KfW). In addition, individual customer requests are taken into account in the planning. Finally, the technical data of the ventilation systems used flow into the ventilation planning.

You should definitely pay attention to this when planning the ventilation

inVENTer, as a provider of decentralized ventilation systems, supplies its customers with ventilation concepts and planning proposals tailored to them, which are optimally based on the actual conditions of use. Decentralized ventilation systems with reversing fans require a balanced air volume flow, which is usually guaranteed by operating in pairs. In the heat recovery mode, the fan changes direction every 70 seconds, with the ceramic core as a heat accumulator being alternately charged and discharged. The calculations are based on the halved air volume flows of the respective devices, as the system later also runs in heat recovery mode as standard and the pendulum mode actually removes air only in half of the operating time. Customers should generally pay attention to this when commissioning ventilation concepts for their construction projects.

Lüftungskonzept und Beratung
Lüftungsplanung - Was muss ich beachten?

Compared to numerous competitors, inVENTer deliberately does not use the highest performance level of 100 percent. As a rule, it is only used to cope with load peaks and is not intended for long-term operation. Pure exhaust air systems are also taken into account in the energetic consideration. These do not have any heat recovery options. Here – as the name suggests – the air is only discharged to the outside. Within the usage unit, however, all fans in the network form the complete ventilation system. This is relevant for the overall calculation of the degree of heat provision, as pure exhaust fans reduce this accordingly due to the lack of heat recovery. As a result, a ventilation concept from inVENTer generates real degrees of heat provision.

Schnellkontakt
close slider

    Welcome to inVENTer

    Your ventilation expert will contact you as soon as possible!


    Mo – Thu: 07:00 – 16:30 Uhr
    Fr: 07:00 – 15:00 Uhr